DE EN TR open the System Schröders - door
engineering drawing ES-2

Fire resistance door class E

System Schröders ES-2

Double-leaf fire door ES-2/120

Fire resistance period 120 minutes
Fire resistance test
in accordance with
EN 1634-1 (European standard)
Tested at Warrington Fire Research, Warrington / UK
Certificate WFRC 346218 B
Resistance to positive and negative pressure
(optional)
up to 5,000 Pa
Options
  • rebated doorleaf
  • rectangular glazing
  • circular glazing
  • stainless steel
 
Technical data
Dimensions
width max. 3,100 mm
heigth max. 3,100 mm
surface area per door leaf max. 3.9 m²
Doorleaf single-acting leaf of mild steel,
galvanized / stainless steel
steel sheets bonded with core material for extremely smooth surface
doorleaf weight ~ 20 kg/m²
debated doorleaf - thickness: 68 mm

steel sheet - thickness: 0.8 - 1.6 mm
Optional Glazing clear dimensions variable to a maximum of 800 mm x 800 mm
- rectangular glazing
- circular glazing ∅ 450 mm (clear dimension)
Hardware solid mortise latch and lock
dogbolt on hingeside
2 hinges
Self-closing doorcloser EN 1154 Dorma TS83 Code IMM
1 spring hinge as standard for rebated door
Handles heavy cast-iron handles with plates or other handles / plates
assemblies admitted for mounting on fire doors
Antipanic-system door leaf can be equipped with antipanic lock and antipanic bar
Frame steel doorframe
1.5 - 3 mm galvanized or stainless steel
with steel reinforcements for hinges and doorcloser