Fire resistance doorset according to European standard EI260
System Schröders TSN-4 CE | |
---|---|
Double-leaf fire resistant steel doorset / gate EI260-Sa4-C5-according to EN 16034 |
|
labeled |
|
Fire resistance |
EI260-Sa4 tested according to EN 1634-1
|
Thermal transmittance |
UD-value ≥ 1.5 W/(m²K) according to EN ISO 10077-1 |
Combinable with additional performance characteristics: |
|
Smoke control
(optional) |
S200 tested according to EN 1634-3 |
Burglar resistance
(optional) |
RC4 - classification report no. 22-7/15.123, PIV-Velbert
according to DIN EN 1627 ff |
Acoustic performance
(optional) |
up to RW (C;Ctr) = 48 (-1;-5) dB according to EN ISO 10140-1 / EN ISO 10140-2 / EN ISO 717 |
Air tightness
(optional) |
up to class 3 according to EN 12207 (up to 600 Pa) expert opinion no. 40-40/12.120, PIV Velbert |
Resistance to wind load
(optional) |
up to class C4 (up to 2,000 Pa) according to EN 12210 expert opinion no. 40-40/12.120, PIV Velbert |
Watertightness
(optional) |
up to class 3A according to EN 12208 expert opinion no. 40-40/12.120, PIV Velbert |
Resistance to positive and negative pressure
(optional) |
up to 3.800 Pa according to DIN EN 12211 expert opinion no. 40-52/16.120 |
Behaviour between different climates
(optional) |
class 2 (d + e) according to EN 12219 (deflection) |
Ability to release
(optional) |
according to DIN EN 16034
according to DIN EN 14351-1 |
Flush with surface
(optional) |
flush-mounted design FLAT |
Explosion protection
(optional) |
For installation in potentially explosive areas, please see confirmation letter Explosion protection ATEX for System Schröders hinged doors (in German language) (PDF) |
Technical data | |||||||
---|---|---|---|---|---|---|---|
Dimensions
(shell dimension) |
|
||||||
Door leaf |
leaf thickness 68 mm to 69 mm - smooth double-walled
|
||||||
Frame |
with elastic rubber seal |
||||||
Floor seal |
required for smoke control, acoustic performance, air tightness
|
||||||
Glazing
(optional) |
glass dimensions and -form variable minimum frieze width: 130 mm
glass inset bars with concealed screw connection (for rectangular glass inset) |
||||||
Hinges |
per leaf 2/3-part KO door hinges
|
||||||
Fittings |
active leaf
for version RC: Protective fitting ES-1 up to ES-3 |
||||||
Locking |
active leaf
single locking according to EN 12209, depending on version multi-point locking
internal snap bolt (locking upwards)
dogbolts at both leafs
|
||||||
Self-closing |
both leafs with door closer according to DIN EN 1154 resp. EN1155 |
||||||
Installation |
|
||||||
Label |
labeled for firedoors according to EN 16034 |
||||||
Optional |
|
||||||
The specifications refer to the usual equipment variants. Individual equipment may be required when combining different performance characteristics. The licensed System Schröders manufacturers will be happy to advise you on planning your requirements. |